TNA DET C631 Conventional Optical Smoke Detector. EN54-7 certified, LPCB approved. Operating voltage: 9.6VDC to 30VDC. Quiescent current: ≤65uA. Alarm current: 18 to 22 mA. Dimensions: 102g (160g with Base DB-6). Operating temperature: -10°C to +50°C. IP42 rated. ABS plastic body (UL94V-0). Price mentioned per piece.
Available sizes
Weight102g (160g with Base DB-6)
Available colors
White
1
Quality inspected
Fast nationwide delivery
7-day return request (terms apply)
The DET-C631 is a conventional (non-addressable) optical (photo-electric) smoke detector designed for general fire detection in commercial and industrial environments. It uses an internal infrared emitter/receiver chamber to detect visible smoke particles from smouldering materials like wood, paper, PVC or foam. It operates over a wide voltage range (9.6 – 30 V DC) and offers low standby current, making it suitable for modern fire alarm loops. It carries LPCB certification and complies with the EN54-7 standard.
Key Features: Wide operating voltage: 9.6 – 30 V DC, nominal 24 V DC; Very low quiescent current: ≤65 µA standby typical; Alarm current: 18–22 mA (typical ~20 mA); Remote LED output drive: Max 20 mA to drive external indicator; Operating temperature range: –10°C to +50°C; Relative humidity: up to 95% RH (non-condensing) at 40°C; Max air velocity: 7.6 m/s — suitable for some airflow environments; Housing: ABS plastic (UL94 V-0 rated), colour: white; Ingress protection: IP42 standard (indoor use); LPCB approved, complies with EN54-7 optical smoke detection standard.
Industrial Uses / Applications: Office buildings and commercial premises; Retail stores, shopping malls; Schools, clinics, educational institutions; Warehouses and storage facilities; Areas where visible smoke detection is preferred (e.g., smouldering fire risk).
Safety Information
Optical smoke detector for conventional fire alarm systems. Install as per manufacturer instructions and local fire safety codes. Test the detector regularly. Clean the sensing chamber as recommended. Do not paint or cover the detector. Replace as per manufacturer guidelines.
Product Data Sheet
Material
ABS Plastic (UL94V-0 Flammability Test Standards)
Brand
TNA
SKU
VZ-PPE-ELEC-075
Model
DET C631
Type
Conventional Optical Smoke Detector
Normal Rated Voltage
24VDC
Operating Voltage
9.6VDC to 30VDC
System Type
Conventional
Quiescent Current
≤65uA
Alarm Current
18 to 22 mA (typical 20mA)
Remote LED Drive Current Output
Max. 20mA
Maximum Air Velocity
7.6m/s
Weight
102g (160g with Base DB-6)
Operating Temp. Range
-10℃ to +50℃
Relative Humidity
95%RH, Non condensing @ 40℃
Alarm LED Indication
Red (Continuous)
Normal LED Indication
Green (Blinking)
Ingress Protection
IP42
Material of Body
ABS Plastic (To UL94V-0 Flammability Test Standards)
Colour of Body
White
Standards
EN54-7
Pricing
Per Piece
Application
Office Buildings and Commercial Premises, Retail Stores, Shopping Malls, Schools, Clinics, Educational Institutions, Warehouses and Storage Facilities
Hot Aerosol Fire Extinguishing Device. Model: QRR0.01G. Automatic fire suppression for electrical panels. Operating temperature: -50°C to +90°C. Service life: 10 years. Extinguishing density: 100 g/m³. Activation time: ≤15 seconds. Compliant with EN 15276-1:2019 & EN 15276-2:2019. Price mentioned per piece.
FLIR K2 Thermal Imaging Camera. 160 x 120 IR resolution. 3" LCD display (320 x 240 pixels). Temperature range: -20°C to +150°C and 0°C to +500°C. Thermal sensitivity: <100 mK. IP67 water-resistant, 2m drop-resistant. Rechargeable Li-ion battery (approx. 4 hours). Includes 2 batteries, charger, strap, power supply, USB cable. Price mentioned per piece.
BRK Electronics 83RN Smoke Alarm. Dual-ionization chamber sensor. Power source: AC 220V + 9V battery backup. Alarm sound level: 85 dB at 10 ft. Operating temperature: 4°C to 38°C. Humidity range: 10% to 90% RH. Dimensions: 5.61" dia x 1.63" height. Weight: 6.4 oz (approx. 0.18 kg). UL 217 & NFPA 72 approved. Price mentioned per piece.